ERROR MESSAGE/ISSUE/SYMPTOMS:
- Low Pressure- this message occurs if the unit drops 4psi below the set sterilization pressure during the sterilization cycle
REALTED MODELS:
- All E, EK, EA, EKA, EZ, EZ10K Models
WHO CAN SOLVE:
- End User & Sales rep- limited
- Technician
CAUSE(S):
- Insufficient water in the chamber
- Faulty heating elements
- Faulty solid state relay (SSR) for the heating elements
- Faulty pressure transducer
- Calibration
- Faulty ajunc3 board
- Faulty Digital Predg board
LEVEL OF TROUBLESHOOTING:
End User Level
- Ensure that the chamber has the proper amount of water, without proper water the unit cannot create steam, without steam the unit cannot pressure. Typically, this causes a low water error and not a low pressure
Adjusting the water inlet time
1- With the unit turned on and sitting idle press the “STOP” button (may have to press it multiple times) until your display screen reads “CODE 102”.
2- With “CODE 102” on your screen press the “UP” arrow to change the display to read “CODE 105” (3 presses)
3- With “CODE 105” on the display screen press the “STOP” button one more time.
4- After pressing the “STOP” button again the display screen will show “WATER INLET ###” that number that you will see is the current setting for the water fill at the start of the cycle.
5- Use the “UP” or “DN” arrow to adjust the water fill to the desired time
6- After changing it to the desired time press the “STOP” button one more time to exit out of the water fill programming.
- If the unit continues to fail a technician will be needed to troubleshoot further
Technician Level
Ensure all user level steps have been completed
Testing the heating elements
- Unplug the unit and remove the covers
- Remove the insulation blanket from around the chamber
Take an ohm reading on the terminals for the heating element, the chart below shows the proper readings. If the readings are incorrect replace the heating elements. (img.15 and img.16)
img.15- ohm and amp
img.16- heaters.1
Take an ohm reading from the heating elements to ground. If the meter reads O/L there is no short to ground in the heating elements and proceed to the next step. If the meter reads anything other than O/L there is a short to ground in the heating elements and all of the heating elements need to be replaced. (img.17)
img.17- heaters.2
Testing the Solid State Relay (SSR)
- Unplug the unit and remove the covers
Label and remove the wiring from the SSR. The SSR for the heating element is located below the ajunc3 board. (img.18 and img.19)
img.18- ssr.1
SSR with plastic cover removed
Terminals 3 & 4- input- 5VDC
Terminals 1 & 2- output- Line voltage (AC)
img.19- ssr.2
- Check for a short circuit between terminals 3 & 4, 1 & 2, 3 & 1, 4 & 2, 3 & 2, 4 & 1. Make sure there are no direct shorts. If a direct short is found in the SSR, replace it. If the meter reads O/L proceed to the next step.
- Check for an open between terminals 1 & 2. Be sure to reverse the meter leads and check in the opposite direction. Repeat the procedure for terminals 3 & 4. If an open (O/L) is found, replace the SSR. If the meter does need read O/L, proceed to the next step
Reconnect the wires to the four connectors of the SSR
Testing the SSR- terminals 3 and 4
Ensure that dip switch #4 on the back of the Digital Predg board is off (down position), if the #4 dip switch is on (up) turn it off prior to proceeding (the #4 dip switch is normally off for 120v units and normally on for 230v units). Dip switch #4 is a preheat function, if it is on the heaters will heat once the unit is powered on (img.20). We need the heaters to be off for the next step.
img.20- dip sw
- Plug the unit back in and power it on, ensure that the unit is sitting idle not running a cycle.
- Take a DC voltage reading from terminal 3 on the SSR to ground, there should be a voltage reading between 3.5v and 5v DC. Afterwards take a DC voltage reading from terminal 4 on the SSR to ground, there should be a voltage reading between 3.5v and 5v DC. A good reading indicates that the SSR is not turned on.
- If terminal 3 reads properly skip the below testing the power supply section. If terminal 3 does not read between 3.5v and 5v DC, check the power supply to ensure that it is providing the proper voltage. The power supply (circled blue below) is mounted above the ajunc3 board. Unplug the unit and disconnect the output connection from the ajunc3 board (circled white below). (img.21)
Testing the Power Supply
img.21- power supply.1
Plug the unit back in and power it on, take a DC volt reading between the red and black wires. A good reading is 12v DC. (img.22)
img.22- power supply.2
Take a DC volt reading between the orange and black wires. A good reading is 5v DC. If the power supply is not reading 5v and 12v DC, replace the power supply. If the readings are correct proceed to the next step to continue testing the SSR.
img.23- power supply.3
Testing the SSR- terminals 3 and 4 continued
- If terminal 4 reads correctly skip this next step. If terminal 4 does not read the correct voltage, unplug the unit and remove the wire on terminal 4. Turn the power back on and take a DC voltage reading from terminal 4 on the SSR to ground, there should be a voltage reading between 3.5v and 5v DC. If the reading is still not correct, replace the SSR. If the reading is correct, proceed to the next step
If the reading is correct, check continuity between the terminal #4 wire and the appropriate connector; unplug the unit when taking this reading. JP4 is the connection for checking the Heater SSR. (img.24 and img.25)
img.24- ssr.3 img.25- ssr.4
If there is no continuity replace the wiring. If there is continuity and the terminal 4 reading is still incorrect the unit has a control problem, replace the Digital Predg board.
Testing the SSR terminals 1 and 2 for 110v units
- Turn the unit on and ensure the dip switch #4 is still off, the heaters must be off for this next step.
- Terminal 2 of the SSR should read between 110v and 125v AC to ground. Terminal 1 should read near 0 volts AC to ground. Reading across terminals 1 & 2 should show between 110 and 125 volts.
- If terminal 2 does not read between 110 and 125 volts to ground, there is a problem with the line voltage wiring going to the SSR.
- If terminal 1 shows the same voltage as terminal 2, replace the SSR. If there is a voltage reading less than 100 volts across terminals 1 & 2, replace the SSR.
Power the unit off so we can enter the in/out test on the unit so we can energize the heaters, this next step must be done with the heaters on. Prior to powering the unit on press and hold the up arrow on the keypad. Continue holding up as you power the unit on. Once the screen comes on release the up button. Press and release the up button to advance to the next step in the in/out test, stop pressing up once the screen displays Heaters. If you accidentally advance past the Heaters option, power the unit off and repeat the steps.
In/Out Test menu order
img.26- in/out test
- Terminals 1 and 2 should each read between 110 and 125 volts to ground. If terminal 2 does not show between 110 and 125 volts to ground, there is a problem with the line voltage wiring to the SSR. If terminal 1 does not show between 110 and 125 volts to ground, replace the SSR.
- Reading across terminals 1 and 2 should show close to 0 volts. If the reading across terminals 1 & 2 is greater than 1 or 2 volts, replace the SSR
Testing the SSR terminals 1 and 2 for 230v units
- Turn the unit on and ensure the dip switch #4 is still off, the heaters must be off for this next step.
- Terminal 1 of the SSR should read between 110v and 125v AC to ground. Terminal 2 of the SSR should read between 110v and 125v AC to ground. If terminals 1 and 2 do not each read approximately 110 volts to ground, there is a problem with the line voltage wiring going to the SSR.
- A reading across terminals 1 & 2 should show between 220 and 235 volts. If a voltage of between 220 and 235 volts is not present across terminals 1 & 2, unplug the unit and remove the wires.
- Plug the unit back in and carefully take a reading across the wires. If a voltage between 220 and 235 is present across the unconnected wires, the SSR needs to be replaced. If the voltage is still incorrect, the problem is with the line voltage wiring going to the SSR.
Power the unit off so we can enter the in/out test on the unit so we can energize the heaters, this next step must be done with the heaters on. Prior to powering the unit on press and hold the up arrow on the keypad. Continue holding up as you power the unit on. Once the screen comes on release the up button. Press and release the up button to advance to the next step in the in/out test, stop pressing up once the screen displays Heaters. If you accidentally advance past the Heaters option, power the unit off and repeat the steps.
In/Out Test menu order
img.26- in/out test
- Terminal 1 of the SSR should read between 110v and 125v AC to ground. Terminal 2 of the SSR should read between 110v and 125v AC to ground. If terminals 1 and 2 do not each read approximately 110 volts to ground, there is a problem with the line voltage wiring going to the SSR.
- A reading across terminals 1 & 2 should show a voltage near 0 volts AC. If the voltage reading across terminals 1 and 2 is higher than 5 volts, replace the SSR.
- If the SSR tests properly proceed to the next step
Insufficient water- typically causes low water message not low pressure
- Check for any clogs in water filter (white plastic filter), the water plumbing lines, and the filter strainer (img.81)
img.81- water filters img.81- water filters
Checking the Water Pump and Water Pump Control
Verify that the water pump is functioning by accessing the in/out test.
1. Power the unit off
2. While the unit is off press and hold the Up-arrow button
3. Continue holding the Up-arrow button and power the unit back on, once the unit beeps twice, let go of the UP and the water pump should be energized, the water pump can be energized twice during the in/out test in case you miss the first selection (img.39). Check to see if you are getting proper line voltage to the water pump (img.40 and img.41).
img.39- in/out test wp
- If the water pump is getting voltage but not running, replace the water pump. The water pump is mounted to the base of the unit between the electronic box and the water reservoir (img.40)
img.40- wp
img.41-elec box
- If the water pump is not getting voltage check the fuse in the back of the unit (img.42) to make sure that it hasn't blown, if the fuse is blown, replace it.
img.42- wp fuse
- If the fuse is not blown check the input voltage connection at the Ajunc3 board (img.43) for the Solid-State Relay (2nd connection from the left of the board).
img.43- wp ssr connect
Checking the SSR
The Water Pump SSR is located in the Electronic Box. Terminals 1 and 2 are on the high voltage side of the SSR that supplies power to the Water Pump. Turn the power off; remove the wires connected to terminals 1 and 2 of the Water Pump SSR. Connect these two wires together and turn the power back on. If the
Water Pump does not run:
- Check that there is power between the wire on terminal 1 and
ground. - Turn the power off and check continuity from the wire on
terminal #2, through the Molex connector pin 11 to the Water
Pump. - Check continuity from the return wire on the Water Pump to the return side of the Circuit Breaker.
- If the SSR has power and there is continuity to and from the water pump, the problem is with the pump, and it should be replaced.
- If the pump does run, the problem is with either the Water Pump SSR or the control circuit.
- Check if the Water Pump SSR is being told to turn on. With a DVM read between TP13 and TP1, on the test point board, a 0 to 1 volt DC signal tells the Water Pump SSR to turn on and 10 to 12 volts tells it to turn off. An incorrect signal would indicate a problem with the control
circuit. - If the control signal is correct at the test point, check if the correct signal is at the Water Pump SSR.
- Terminals 3 and 4 are on the control side of the SSR and are connected to JP15 on the Ajunc3 board.
- A reading across terminals 3 and 4 should show 10 to 12 volts DC for the Water Pump SSR to be turned on and 0 to 1 volt if it should be off.
- If the control signal is not correct at the Water Pump SSR, the problem is with the Ajunc3 board, and it should be replaced. After replacing the Ajnuc3 board the new board will need to be recalibrated (see calibration section of this troubleshooting guide).
Checking Exhaust Solenoid for a Leak
- If the water pump is not the cause of the failures the next most likely cause is the exhaust solenoid valve. If the exhaust solenoid is leaking, you will notice water dripping out from the open end of the copper condensing coil in the water reservoir after the unit starts to build pressure.
- Either start a cycle and periodically look into the water reservoir (use caution there will be steam and steam will be hot) to see if any water is dripping from the coil or disconnect the coil from the fitting inside the reservoir (img.44) and see if steam and/or water is coming out from the opening (use caution steam will be hot).
img.44- cc connect
- If you would prefer to inspect the solenoid instead of running a cycle and looking for a leak or, if you notice a leak during the test cycle you should open the solenoid valve (when the unit is powered off and no pressure is in the chamber) and look for any debris and/or cracks in the seat of the valve.
- Also inspect the solenoid plunger for tears.
- The exhaust solenoid valve will be mounted to the base of the unit and be connected to a copper plumbing line that elbows up from it and connects to the water reservoir (solenoid to the condensing coil). On any 2340EA/EZ9 or 2540EA/EZ10 it will be the rear most solenoid valve on the base in the unit (img.45), on a 3870EA it would be the front most solenoid on the base in the unit (img.46).
2340EA/EZ9 and 2540EA/EZ10
img.45- sol9/10
3870EA
img.46- sol38
img.47- sol.1
img.48- sol.2
- If the solenoid is dirty or has debris clean it and try running another cycle. If the valve continues to leak or the valve is cracked, and/or no debris is found replace the solenoid.
Air Outlet Solenoid Valve
- If the exhaust solenoid is good, check the air outlet solenoid (may not be labeled with 41 like in the photo below) on the back of the reservoir (img.49) for cracks and/or debris as well by opening the solenoid valve.
- If the air outlet solenoid is leaking it would be leaking steam back into the water reservoir tank from where the solenoid connects and it would be very difficult to see by looking into the water reservoir with the unit running.
img.49- sol.3
Testing the Water Electrode
If the Water Electrode in the chamber is clean but the unit is still failing, you can test the water electrode to see if it is bad. Power the unit off, press and hold the Up-arrow button, continue holding the Up-arrow button and power the unit on to enter the in/out test. The electrode is the last option in the in/out test (img.50).
img.50- in/out water elect
With the chamber empty the screen should read 001, put water in the chamber of cover the electrode with a wet paper towel and see if the value changes. If the value does not change, power the unit off and remove the green wire from the water electrode, once disconnected re-enter the in/out test mode. With the water electrode wire disconnected, the display screen should show 001. Ground the wire by touching it against the chassis of the unit and see if the value changes, a ground signal would signify a full chamber of water, if the value does change when testing performing this test the water electrode is faulty and needs to be replaced. If the value does not change when performing this test, trace the green wire back to where it connects on the Ajunc3 board and test continuity through the wire to ensure the wire isn't the issue, if the wire tests ok the Ajunc3 board is faulty and should be replaced, a new Ajunc3 board would need to be recalibrated (see calibration section of this troubleshooting guide).
Testing the Pressure/Calibration
- Calibration is also uncommon to cause a low pressure reading, typically calibration will result in- High temperature, high pressure, low heat, low water
Disconnect the copper line from the top rear chamber manifold that connects to the pressure transducer (img.27)
img.27- pressure test.1
Connect a pressure gauge in its place and reconnect the copper line from the pressure transducer to the pressure gauge (img.28)
img.28- pressure test.2
Run a test cycle and verify that the pressure reading from the display screen matches the pressure gauge reading. If the pressure readings do not match, proceed to the calibration instructions (img.29 - img.38). If both pressure readings match the issue is not the pressure transducer or the calibration and proceed to the next section
Calibration
If the Air Outlet Solenoid Valve is not the problem but the pressure reading is still too high causing the failure the issue is most likely calibration. Calibration would require the Tuttnauer TEST-9 calibration kit.
img.29- cal.1
img.30- cal.2
img.31- cal.3
img.32- cal.4
img.33- cal.5
img.34- cal.6
img.35- cal.7
img.36- cal.8
img.37- cal.9
img.38- cal.10
- If the pot 2 adjustment cannot be made, replace the pressure transducer. If the issue persists with a new pressure transducer replace the ajunc3 board.
- If the calibration voltage reading for pot 2 is correct but the display screen pressure reading is still inaccurate from the pressure gauge replace the Digital Predg board
SOLUTION:
- Adjust water inlet time
- Replace water pump
- Resolve the leak
- Replace faulty heating elements
- Replace faulty solid state relay (SSR) for the heating elements
- Replace faulty pressure transducer
- Calibrate the unit
- Replace faulty ajunc3 board
- replace faulty Digital Predg board
Comments
0 comments
Please sign in to leave a comment.